In industrial use the ambient temperature considered is usually 35oC. If uses in a marine environment temperature of 40oC (Restricted areas) and 45oC (unrestricted areas) are used, therefore the circuit breaker rating may be 'free air' value and this does not consider the degree of ventillation, the number and position of the circuit breakers or the layout of the bus bars. The final switchboard arrangement could be only 80 to 90% of the free air rating
Blow force at right angles to arc and field.
Hot ionised gases around the arc and contacts are displaced by cold air forming eddy current air flow. This helps to increase resistance between contacts.
Voltage rating
At medium voltages the phase to neutral voltage may be 250v but the potential difference between two phases with the neutral insulated would be 440v. At these voltages no difficulties should arise in selecting the circuit breaker equipment.
However, on a 3.3kV insulated neutral system the phase to neutral voltage is 3.3kV/Ö 3 = 1.9kV. If an earth fault develops on one phase the potential of the other two phases to earth is 3.3kV. To ensure the insulation is not subject to excessive stress a circuit breaker designed for a normal system voltage of 6.6kV may be fitted. Also on insulated neutral systems high over voltages may be caused by arcing faults. Medium voltage systems switch gear insulation should be able to withstand such voltages, but 3.3kV and above, the margin of safety is reduced. When a high voltage system is installed both the voltage rating of the circuit breaker and the method of earthing must be considered.Current rating
Consider three factors;
Fault rating
Breakers should be rated to accept a breaking current of about 10 times the full load current. The breaker should also be able to make against a fault condition where the making current may be 25 times the full load current when the contact first make. Circuit breakers must remain closed for a short time when a fault occurs in order to allow other devices which are nearer to the fault to trip first. The breaker should be capable of carrying its breaking current for a specified time of usually about one second.
Arc suppression

The blow out coils, which are connected in series with the circuit breaker contacts, form an electro-magnetic field which reacts with the arc to give a deflecting force which tends to bloe the arc outwards. The increase in effective length of the arc causes it to extinguish more quickly. The blow out coils are protected form the arc by arc resistant material which may be in the form of an air shute.